Post-Mortem of AWS Outage

[Self-post because it's not easily linkable] We would like to share some detail about the Amazon Elastic Compute Cloud (EC2) service event last night when power was lost to some EC2 instances and Amazon Elastic Block Store (EBS) volumes in a single Availability Zone in the US East Region. At approximately 8:44PM PDT, there was a cable fault in the high voltage Utility power distribution system. Two Utility substations that feed the impacted Availability Zone went offline, causing the entire Availability Zone to fail over to generator power. All EC2 instances and EBS volumes successfully transferred to back-up generator power. At 8:53PM PDT, one of the generators overheated and powered off because of a defective cooling fan. At this point, the EC2 instances and EBS volumes supported by this generator failed over to their secondary back-up power (which is provided by a completely separate

Why it failed

[Self-post because it's not easily linkable] We would like to share some detail about the Amazon Elastic Compute Cloud (EC2) service event last night when power was lost to some EC2 instances and Amazon Elastic Block Store (EBS) volumes in a single Availability Zone in the US Eas

Kind
startup
Status
Shut down
Inventor
dlgeek
Ended
2012
Source
hackernews